A duct network is one system and the fan is one part of it. Enter the friction and local losses of each segment, the flow split across parallel branches and the pressure required at the terminal; the system solves the operating point against the fan curve and checks every segment's velocity.
The whole network in one solve:Enter diameter or cross-section, length, material and local loss coefficients per segment; the system sums the network resistance at a given flow instead of looking at the fan alone.
Resistance and fan curve combined:The network resistance curve is solved against the chosen size's performance curve by bisection to find working flow and pressure, reporting flow offset and pressure margin.
Parallel branches balanced automatically:Parallel branches split flow on the rule that pressure drop is equal across branches and branch flows sum to the trunk flow, with each branch's deviation from design flow reported.
Per-segment velocity checks:Each segment's actual velocity is compared with the recommended range: too low deposits dust, too high causes whistling and wear, and out-of-range segments are flagged.
FAQ
Does it work for a single fan?
Yes. A single fan is one series path from inlet to terminal, and the system still reports the operating point and per-segment checks; add more fan positions to split pressure between a main and booster fan.
How is leakage handled?
As a selection multiplier: process flow times a leakage factor gives the selection flow. The factor follows ductwork tightness, and both the process and selection values are shown.
What if the terminal is under negative pressure?
Terminal pressure accepts negative values to represent a required negative pressure (for example downstream of a collector or upstream of a clean area); it enters the solve with its sign.